- BVM150 System of 16 BVM units CJ-59092
- BVM300 System of 31 BVM units CJ-59093
- BVM600 System of 61 BVM units CJ-59096
The BVM equipment is a battery cell/block voltage measurement system performed on battery banks. It can be used in conjunction with a load device such as the TORKEL. It can also be used to measure cell/block voltages from a PC with TORKEL Win or PowerDB. The BVM system is designed in a modular form where one BVM unit is used for each cell or block in the battery string to be tested. One BVM unit for each cell or block connects to the next in a daisy chain fashion.
The included dolphin clip can easily be removed and exchanged with different styles of standard banana plug clamps and/ or extension cables to accommodate any battery connection requirement.
Up to 2 x 120 BVMs can be daisy chained in a single battery bank under test that is used for the capacity testing of large, industrial battery banks commonly found in electrical power substations, telecom facilities and UPS systems generally. When used in conjunction with a load device (e.g. Megger TORKEL) and test data management software (TORKEL Viewer, PowerDB or TORKEL Win) the BVM system facilitates the execution of an automated battery bank capacity test, according to IEC and IEEE standards. The test also meet NERC/FERC requirements. The BVM-system is designed in a modular form where one BVM device is used for each battery cell or “jar” in the string to be tested. One BVM for each battery connects to the next in a “daisy-chain” fashion, thereby providing easy and economical expandability to meet the testing requirements for small-tolarge battery bank systems. Setting up the BVM system for a test is quick and easy. Each BVM unit is identical and can be connected in any battery test position, thus providing maximum flexibility and interchangeability of the BVMs. The
BVM “Auto Discovery” feature enables the host device to automatically determine the number of batteries under test and provide sequential identification of each BVM unit in the test string.
Application:
Each BVM unit is identical and can be connected in any battery test position. A single cable connects the first BVM unit in the string to a Power & signal connector. The BVM system data output is connected via an Ethernet cable to the BVM USB port on TORKEL 900 or to a PC with data management SW, e.g. PowerDB or TORKEL Win. The BVM system can also be used together with older Megger TORKEL versions, or any battery load bank. This will require the use of a separate PC with test management SW e.g. PowerDB or TORKEL Win.